To order transmitters use the following method to create a part number:
TS followed by the sensor calibration and the required temperature span in
degrees Fahrenheit.
Example-TSJ500= TS type transmitter, Thermocouple type J, 0-500°F.
In
Head Transmitters
|
||
Specifications | Description | |
RTD inputs (0.00385 or 0.003916) | 3 wire sensor, -200 to 1000°C / -328 to 1832°F | |
Thermocouple inputs | AE, B, E, J, K, L, N, R, S, T, U | |
Maximum sensor wire resistance | 25 Ohm/Wire | |
Sensor failure monitoring | Upscale or Downscale | |
Output, Analog | 4-20, mA, temperature linear | |
Ambient, storage and operation Temperature | -40 to 85°C / -40 to 185°F | |
Isolation in/out | Non isolated | |
P | 8 to 36 VDS 2-wire | |
Accuracy-RTD's | ±0.2% | |
Accuracy-Thermocouples | ±0.3% | |
Cold Junction Compensation for T/C | ±0.5°C / ±0.9°F | |
Housing Construction | PC + ABS plastic | |
Mounting (in head or din rail with kit) | DIN B-Head or larger, or DIN rail (with Kit) | |
Connection | Single or stranded 16 AWG | |
Weight | 50 Grams |